Description
A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault.
References1
Metrics
- CVSS 4.0
-
8.7
HIGH
Score source: CNA
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X - EPSS — exploit probability
- 0% percentile: 28 · as of 11 November 2026
- CWE
- CWE-763
Could this be exploited in your environment?
A patch closes the known hole. A penetration test shows what an attacker can still reach — with proof.